- 品牌/商標:民域
上海民域電氣有限公司從事高壓電氣產品產品生產銷售,高壓負荷開關、真空斷路器、隔離開關、接地開關、高壓熔斷器、避雷器、絕緣子、穿墻套管、電力金具等系列產品。
CFH-70/240穿刺式防弧線夾
一、產品介紹
CFH 型防弧線夾是一種新型結構的產品,其主要安裝在線路絕緣子的負荷側,具有防止10-20KV 架空導線雷擊斷線功能。安裝施工方便,性能可靠,為電力部門提供了一條投資少收效大的有效措 施。根據用戶需要采用剝皮型的非穿刺式防弧線夾型號為:CFH-50/240B; 穿刺式防弧線夾型號為: CFH-50/240。
二、CFH-70/240穿刺式防弧線夾結構特點
?主要由絕緣護罩、壓緊螺母、穿刺壓塊、線夾座、引弧棒和絕緣套管等組成。
?引弧棒和線夾座裝配連接咸體,當雷擊發生時,引弧棒和絕緣子(或橫擔)金屬件之間放電,使續流工頻電弧 移動到引弧棒上燒灼,從而保護絕緣導線不受損傷。
?CFH-50/240型穿刺式防弧線夾具有穿刺式的刺齒構造,安裝施工方便,不需剝除絕緣導線絕緣層,避免線芯進 水和腐蝕,臧輕操作人員的勞動強度。
?能耐受多次工頻大電流電弧的燒灼
三、CFH-70/240穿刺式防弧線夾放電間隙安裝尺寸表
安裝支柱型號 放電間隙/mm
P-10絕緣子 125mm-135mm
P-15絕緣子 140mm-150mm
P-20絕緣子 150mm-170mm
PS-15絕緣子 150mm-170mm
PS-20絕緣子 170mm-180mm
S-20瓷橫擔絕緣子 270mm-300mm
四、CFH-70/240穿刺式防弧線夾型號規格和性能參數
型號規格 | 絕緣導線截面mm2 | 雷電全波沖擊耐受電壓(峰值)KV | 1min工頻耐受電壓 (有效值)KV | 工頻電弧電流(有效值)KA | 備注 | |
干 | 濕 | |||||
CFH-70/240 | 70/240 | 75 | 42 | 30 | 12.5 | 穿刺式 |
CFH-70/240B | 70/240 | 75 | 42 | 30 | 12.5 | 非穿刺式 |
五、穿刺式防弧線夾CFH-70/240安裝方法
1本產品安裝在線路絕緣子(例如P-15柱式絕緣子)的負荷側,剝皮型的按示圖2要剝開絕緣層6580mm左右, 把防弧線夾緊固在導線上,穿刺式的夾線方式有2種 (1)力矩螺母的緊固方法將絕緣導線盡量平行卡進線夾槽 內,先用手擰緊力矩螺母,再用套筒扳手交替均勻擰緊至力矩螺母頂端脫落為止。(2)根據導線截面積及天氣溫度 設定扭力扳手扭力值2635Nm,用扭力扳手交替、對稱擰緊2個壓力螺母,用肉眼檢查導線絕緣層貼緊線夾弧 槽,看不見剌齒根都即可。然后擰緊備緊螺母,防止壓力螺母松動。
2安裝時按示圖及放電間隙安裝尺寸表調整本產品和線路絕緣子之間的距離。
3絕緣護罩安裝在線夾座的外部,用固定扣固定絕緣護罩。(具體請參照產品安裝說明書
Five, the piercing type arc clip CFH - 70/240 installation method
1 this product is installed in the line insulator, such as P - 15 column type insulator) load side, skin type as shown in figure 2 to strip away the insulation around 6580 mm, the arc clip fastening on the wire, the piercing type clip wire way of two (1) the torque nut fastening methods will be insulated wires parallel card as far as possible into the clamp groove, tightening torque nut by hand, and then tighten evenly to alternately with socket wrench moment off the top nut. (2) according to the cross-sectional area and the weather temperature setting torque wrench 2635 nm torque values, alternately with torque wrench, tighten nut 2 pressure, with the naked eye check wire insulation against clamp arc groove, invisible might root all can. Then tighten the nut, prevent pressure nut is loose.
Installed 2 according to the chart and the discharge gap size table to adjust the distance between this product and line insulator.
3 insulation shield installed online external holder, buckle with fixed fixed insulation shield. (please refer to the product installation instructions